ETIM Class
Switch disconnector
Version as main switch
Yes
Version as safety switch
No
Version as maintenance-/service switch
No
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Suitable for floor mounting
No
Suitable for front mounting 4-hole
Yes
Suitable for front mounting centre
No
Suitable for distribution board installation
Yes
Voltage release optional
No
Number of auxiliary contacts as change-over contact
0
Motor drive integrated
No
Version as reversing switch
No
Version as emergency stop installation
No
Rated operating voltage (V)
750 - 750
Max. rated operation voltage Ue AC (V)
690
Conditioned rated short-circuit current Iq (kA)
50
Rated short-time withstand current lcw (kA)
2.5
Rated operation power at AC-23, 400 V (kW)
45
Switching power at 400 V (kW)
45
Rated operation power at AC-3, 400 V (kW)
45
Rated permanent current at AC-23, 400 V (A)
90
Rated permanent current Iu (A)
125
Rated permanent current at AC-21, 400 V (A)
125
Type of control element
Other
Degree of protection (NEMA)
1
Degree of protection (IP), front side
IP20
Type of electrical connection of main circuit
Cable clamp
Device construction
Built-in device fixed built-in technique